HQC135 & HQC200 QUICKCHILLERSMODELHQC135 ML-124069HQC200 ML-124070701 S. RIDGE AVENUETROY, OHIO 45374-0001937 332-3000www.hobartcorp.comFORM 3464
– 10 –Product Probe AssemblyThe product probe junction box is assembled onthe side wall panel behind the door hinges.Remove the cover from the product
– 11 –Temperature Control SensorsPush the three refrigeration temperature control sensors down through TUBE #3 (Fig. 8) from theelectrical box on top
– 12 –Fans and Defrost HeatersBring all connector blocks from the coil and fan section (fans and defrost heaters) up through TUBE #3and TUBE #4 to the
– 13 –ELECTRICAL CONNECTIONSWARNING: ELECTRICAL AND GROUNDING CONNECTIONS MUST COMPLY WITH THEAPPLICABLE PORTIONS OF THE NATIONAL ELECTRICAL CODE AND/
– 14 –INSTALLATION — REMOTE CONDENSING UNITSPrior to installing the condensing unit, test the electrical service to assure that it agrees with thespec
– 15 –PIPE SIZING GUIDELINESPiping design and line sizing is the responsibility of the installer. The following table can be used asa guideline. The
– 16 –WATER COOLED CONDENSING UNITSWater cooled condensing units are equipped with water valves which control the rate of water flowthrough the conden
– 17 –* Reproduced from Copeland Technical Bulletin AE 1174-R6, dated 1/1/85.WATER FLOW REQUIREMENT FOR COPELAND WATER COOLED CONDENSING UNITS *Gallon
– 18 –OPERATIONCONTROLS (Fig. 19)Fig. 19START-UPThe screen at left is displayed when the chiller is firstturned on.OVER TEMPERATUREIf CAUTION HI AIR 1
– 19 –PRINTER SUPPLIESPrinter supplies are available from your local Hobart sales and service office.The standard printer uses 21/4" thermal prin
– 2 – HOBART CORPORATION, 2001Model HQC135 QuickChiller Model HQC200 QuickChillerTABLE OF CONTENTSGENERAL . . . . . . . . . . . . . . . . . . . . . .
– 20 –BY TEMPERATURETYPE: SOFT CHILL↓TARGET TEMP: 37°F↑MAIN STARTMAIN MENUBY TEMP —Chill Cycle is complete when any (or all) product probe(s)
– 21 –SELECT PROBE:1 39°F DONE 32 44°F 48°F 41:16:08 CONTINUESELECT PROBE:1 39°F REMOVE 32 44°F 48°F 41:16:28 CONTINUE• Press ADD/
– 22 –HOLDING AIR: 14°F1 39°F 42°F 32 44°F 40°F 40:00:11 STOP/RESETBY TIMETYPE: SOFT CHILL↓CYCLE TIME: 01:30↑MAIN STARTMAIN MEN
– 23 –• Select NONE to continue without printing.• Select RECORD to print a Chill Report. If equippedwith the optional label printer, refer to the al
– 24 –MAIN MENUBY PROD —Recalls programmed chill parameters for the product, either BY TEMP or BY TIME.From the Main Menu, select BY PROD.• If two or
– 25 –CHILLING AIR: 14°F 1 159°F 156°F 3 2 154°F 154°F 41:29:57 STOP/RESETIf the selected product was set to chill BY TEMP:• Follow the cycl
– 26 –PRODUCT LISTAny product from the PRODUCT LIST can be chilled using the BY PROD mode, once it has beenenabled in Setup Products (page 28). Only
– 27 –DEFROSTING COIL 12°FTIME REMAINING 19:52 EXITREADY TO DEFROSTREMOVE FOODCANCEL STARTDEFROSTNOT REQUIREDHOLD PROD — After Chi
– 28 –SETUPFrom the Main Menu, select MORE and SETUP.• When you first enter SETUP, only Preset Supervisor isavailable. On the PASSWORD (PIN) line, us
– 29 –SETUPFrom the Main Menu, select MORE and SETUP.• When you first enter SETUP, only Preset Supervisor isavailable. On the PASSWORD (PIN) line, us
– 3 –INSTALLATION — REMOTE CONDENSING UNITS . . . . . . . . . . . . . . . . . . . . . . . 14GENERAL. . . . . . . . . . . . . . . . . . . . . . . . .
– 30 –SYS PAR• From the Main Menu, select MORE and SETUP.• When you first enter SETUP, only Preset Supervisor isavailable. On the PASSWORD (PIN) line
– 31 –• Access the Sys Par 1 menu as shown on page 30.• From Sys Par 1, select CLOCK.CLOCK• Set the Month using the ↓ or ↑ keys.• Select NEXT to move
– 32 –• Access the Sys Par 1 menu as shown on page 30.• From Sys Par 1, select PROBES.PROBES(Probe #’s 1 – 4 should be ON.)• Select any probes marked
– 33 –• Access the Sys Par 2 menu as shown on page 30.• From Sys Par 2, select REMOTE ALARM.REMOTE ALARM• Yes closes the Remote Alarm circuit in the e
– 34 –• Access the Sys Par 2 menu as shown on page 30.• From Sys Par 2, select ALARMS.ALARMS• Use the ↓ or ↑ keys to adjust the DOOR OPEN setting.Rang
– 35 –• Access the Sys Par 2 menu as shown on page 30.• From Sys Par 2, select MODE.MODE• From Mode Parameters, select CHILL.(BACK returns to SYS PAR
– 36 –• Access the Sys Par 2 menu as shown on page 30.• From Sys Par 2, select MODE.MODE• From Mode Parameters, select SOFT CHILL.(BACK returns to SYS
– 37 –• Access the Sys Par 2 menu as shown on page 30.• From Sys Par 2, select BUZZER.BUZZER• Set the VOLUME [0 – 9 ] using the ↓ or ↑ keys.• Set the
– 38 –GLOSSARYAlarms — Sets the buzzer intervals after the Door is Open or when to be notified that theCompressor needs to be Cleaned.Buzzer — The con
– 39 –GLOSSARY cont.Remote Alarm— The chiller can be wired to a remote alarm which will provide notification of certainirregularities: Printer Error,
– 4 –Installation, Operation, Use and Care ofModel HQC135 & HQC200 QuickChillersSAVE THESE INSTRUCTIONSGENERALThe HQC135 QuickChiller is designed
– 40 –MAINTENANCECLEANINGWash, rinse, and sanitize the product probes before and after use as you would any food-contactutensil that measures temperat
– 5 –Fully assembled units have the coil and fan unit, probes and controls prewired. Place assembled unitin final position ready for connection of re
– 6 –PL-5338335617224PANEL ASSEMBLYEach panel is locked in place with the Cam Fastlock using the hex tool supplied (Fig. 3). Each wallpanel is locked
– 7 –PL-41106-1HEX WRENCH IN LOCKING HOLERIGHT SIDE PANELREAR PANELASSEMBLYIf a 3" insulated floor is supplied, position and level floor panel fi
– 8 –INTERNAL ELECTRICAL CONNECTIONSRemove the lid from the electrical box on top of the cabinet (Fig. 8). On the front of the cabinet, removetwo scr
– 9 –Push the four control cables with connectors [ J5 ], [ J7 ], [ J9 ] and [ J12 ] down TUBE #2. Refer to thetable below and Figs. 8 and 10. Conne